- CYLINDER
CONTROL UNIT: Integral
design requires
no separate
release pressure
cylinder - separate
wire cable activation
lines for automatic
fusible link
and optional
remote pull
station provide
an added measure
of safety -
an easily accessible
manual release
mechanism which
provides an
option to the
automatic fusible
link and, depending
on local codes,
can be used
in place of
a remote manual
pull station
- unique fool
proof technique
for achieving
necesssary input
wire cable tension.
- PIPING: Unbalanced
piping network
simplifies application
design and installation
- no separate
piping to connect
system pressure
cylinders to
extinguishing
agent container.
Schedule 40
stainless, chrome-plated
and black pipe
can be used.
- CYLINDERS: (DOT-4BW-225
Rated) - Contain
PyroChem Potassium
Carbonate Solution
stored at 225
psi - pressure
gauge for visual
maintenance
checks - 3.00
and 4.60 gallon
sizes provide
10 and 15 flow
point coverage
respectively,
offering a broad
range of application
coverage, as
well as 6.0
gallon tanks
available when
applicable.
- NOZZLES: Fixed
and Swivel Head
Nozzles have
been established
to relax placement
tolerances.
- REMOTE
MANUAL PULL
STATION: Simple operating
instructions
with a double
action release
avoids careless
system discharge
- a 150' wire
cable run with
1/16th inch
cable and 40
corner pulleys
maximum - a
dedicated wire
cable input
line to the
cylinder head
provides a true
back-up in the
event fusible
links are fouled.
- FUSIBLE
LINK KITS: Accommodates
both series
and terminal
placement to
minimize inventory
and simplify
ordering - all
necessary components
included for
efficient assembly
and installation
- a 350 degree
Fahreinheit
fusible link
standard - other
temperatures
available -
20 fusible links
on a 150' wire
cable run with
40 corner pulleys
maximum provides
substantial
hazard coverage.
- AUTOMATIC
GAS SHUT-OFF
VALVE: Complies
with requirements
pertaining to
the shut-off
of fuel as described
by NFPA 17A
- after regular
maintenance/service
check can be
reset at control
head for convenience
of service technician
- a 100' wire
cable run with
30 corner pulleys
maximum provides
mounting flexibility.
- CORNER
PULLEYS AND
ACCESSORIES: Designed to
ensure reliable
system function,
as tested by
Underwriters
Laboratories.
|